VEX340: Control system
Frost protection
Highly ef cient counter  ow heat exchangers can be prone to
icing as the air extracted from a room can contain moisture.
When the energy from this extracted air is used (when the air
cools), the moisture condenses to water vapour, which collects
in the heat exchanger.
The high ef ciency means that some areas inside the heat
exchanger become very cold, and in these areas water will
freeze and form ice. This can block the air ow. To counteract
this a new control principle has been developed, which
ensures optimal operation.
To ensure EXHAUSTO counter  ow heat exchangers can
operate in areas that have low outdoor temperatures
EXHAUSTO has developed a unique extract air system.
When ice begins to form inside the counter  ow heat exchanger,
the VEX340H control system circulates up to 30 % of the
warmed supply air back into the cold outdoor air. This raises
the temperature, and helps to prevent icing.
To the right side we have the return air principles and below
we have the different frost protection methods.
Innovative ice detection and control
Is an imbalance
acceptable?
Yes No
Yes No
METHOD 3METHOD 1 METHOD 2
Return air is activated and
gradually increased to 30 %
Air ows (supply air and extract air)
are reduced if necessary to achieve
30 % return air
The outdoor air is gradually
reduced
The unit enters hibernation mode
The unit starts every two hours
and monitors the situation
Return air is activated and gradu-
ally increased to 30 % – if possible
The outdoor air is gradually
reduced
The unit enters hibernation mode
The unit starts every two hours and
monitors the situation
Return air is activated and
gradually increased to 30 %
Air ows (supply air and extract air)
are reduced if necessary to achieve
30 % return air
The unit enters hibernation mode
The unit starts every two hours
and monitors the situation
Is reduced extraction
during de-icing
acceptable?
Air  ow control
2. Constant air ow
Constant pressure regulation of extract air
3. Constant pressureregulated extract air with  xed supply air setting
5. Constant pressureregulated extract air with slave-controlled supply air
Constant pressure regulation of supply air
4. Constant pressureregulated supply air with  xed extract air setting
6. Constant pressure regulated supply air with slavecontrolled extract air
Constant pressure regulation of both extract air and supply air
7. Constant pressure regulation of both extract air and supply air
Air regulation - Six different methods of regulation can be selected:
NB! This function is only active for air ow control methods 2 and 5 See below for details.