5
VEX340
VEX340
VEX340 Capacity curves
Capacity curve with F5 lters
SFP curve [J/m
3
]
Operating curves
A = Pressure loss supplement with F7 lter
B = Pressure loss supplement with HCE/HCW
C = Pressure loss supplement with CCW
Capacity calculations are based on conditions given
on our website.
To calculate capacity data, use our product
calculation software on our website.
VEX340 Temperature efciency
The VEX unit temperature efciency is shown at different
volume ow ratios, calculated as:
Supply air
= 0.8 and 1.0
Extract air
h
t
=
t
2.2
- t
2.1
=
Temperature efciency
t
1.1
- t
2.1
t
2.1
= Temperature of outdoor air
t
2.2
= Temperature of supply air
t
1.1
= Temperature of extract air
Efciency without condensation according to EN308
Extract air = 25°C/30% RH - Outdoor air = 5°C/50% RH
Balance between supply air/extract air = 1.0
Efciency without condensation with imbalance
Extract air = 25°C/30% RH - Outdoor air = 5°C/50% RH
Balance between supply air/extract air = 0.8
Efciency with condensation
Extract air = 20°C/55% RH - Outdoor air = -10°C/50% RH
Balance between supply air/extract air = 1.0