7
HCW340 Technical data for water heating coil – accessories
Technical data
Test pressure 3000 kPa
Max. operating pressure 1600 kPa
Number of rows of pipes 1
Number of circuits 2
Face area (HxW) 420 x 520 mm
Pipe connection DN15 (1/2’’)
Fin spacing 1.6 mm
Weight (without uid) 15.5 kg
Water content 1.3 l
Calculation example for water heating coil
Conditions
Water supply temperature 60 °C
Water return temperature 40 °C
Tolerance of calculated results ± 10 %
Volume ow ratio 1.0
Heat recovery 100 %
NB:
For frost protection using glycol, the output values in the table
below must be reduced by approximately 15–20%.
We recommend the heating coil requirements are precisely calculated using the EXselect product
selection software tool on our website, which also includes more comprehensive calculation data.
VEX340 (2000 m
3
/h) / HCW340 heating coil (100 % heat recovery)
Outdoor
air temp./
humidity
Room temp./
humidity
Temp. and
humidity
after exchanger
HCW
output
Supply air
temp./humidity
Water
ow
p HCW
K
vs
p K
vs
p
air side
[°C / %] [°C / %] [°C / %] [kW] [°C / %] [l/h] [kPa] [kPa] [Pa]
-12 / 80 22 / 20 16.0 / 10.0 3.3 22 / 7 144 0.167 0.4 12.97 20
-20 / 85 22 / 20 14.7 / 5.0 4.17 22 / 6.3 183 0.183 0.4 20.84 20
Example of calculated values for the heating coil