CDA HCE340 for Manual de Serviço Página 17

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 24
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 16
17
VEX340: Control system
Technical specications, modules
Dimensional sketch - HMI (control panel)
EXHAUSTO
OK
RD12248-01
EXHAUSTO
Esc
OK
RD12249-01
Control panel
locked mode
Control panel
open mode
Operating
switches
Colour
graphic
display
CONNECTION BOARD
2 x LS
(Closing damper,
exhaust air/outdoor air)
Power supply 24 V DC
ON/OFF 24 V DC
Max. power consumption 0.3 A
BT
(re thermostat/smoke detector)
Max. 4 A breaking current
START/STOP
Digital input
ALARM Change-over relay. Max 8 A @ 30 V DC
or 250 V AC Load Resistance
Communication
Modbus RTU RS-485
TCP/IP (Ethernet/webserver)
MHCW (Control for water heating coil)
MCCW (Control for cold water coil)
MXCU (Control for external cooling unit)
Communication
Modbus RTU RS-485
MVM power supply
24 V AC
MVM control signal
0-10 V DC
Relay contact for circulation
pump
250 V, max. 5 A cos f 0,97
MHCE (Control for electrical heating coil)
Communication
Modbus RTU RS-485
Number power step
Up til 4
Modulating power step
Single-step
Mains voltage
3 x 400 V + N + PE
MIO (Modbus Input Output)
Analogue input 0-10 V DC
Analogue output 0-10 V DC
Digital input 24 V DC
Digital output open collector 1 A
Relay output 250 V max. 8 A, AC1
Temperature in
NTC 10 kV @ 25 °C
CO2 sensor
Control signal, Analogue Output 0-10 V DC
Measurement range 0-2,000 ppm
Accuracy +/- 20 ppm @ 25 °C
Humidity sensor
Control signal, Analogue Output 0-10 V DC
Measurement range 5-95 % RH
Accuracy +/- 3 % RH (30-70 % RH)
PIR sensor
Perspective, horizontal 90 °
Range 6 m
Cut-out delay 10 min.
TS ROOM E / TS DUCT E
Sensor
NTC 10 kV @ 25 °C
Vista de página 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22 23 24

Comentários a estes Manuais