15
VEX340: Control system
EXact control system - List of functions for accessories
Function / component Description
Temperature sensors 1. In the supply air duct to measure/control supply air temperature
2. On the return pipe from the water heating coil to keep the heating coil warm and protect it
from icing
3. To protect external piping linked to the heating coil from icing
4. Temperature sensor on water heating coil supply pipe
Modulating motor valve Valve for variably regulating the ow of water to the cold water coil, depending of the cooiling
requirement
Circulation pump control 1. Control of the water heating coil circulation pump
2. Heat requirement function (keeps heating coil frost-free)
3. Built-in control to run the circulation pump during periods when heating is not required
Function / component Description
Temperature sensors 1. In the supply air duct to measure supply air temperature
2. In the cold water coil supply pipe
Modulating motor valve Valve for variably regulating the ow of water to the cold water coil, depending of the cooiling
requirement
Circulation pump control 1. Control of the cold water coil circulation pump
2. Built-in control to run the circulation pump during periods when cooling is not required
Function / component Description
Temperature sensors In the supply air duct to measure/control supply air temperature
Overheating protection 1. TSA60 is situated on the circuit board, trips at 60 °C and has manual reset on the HMI panel
2. TSA70 is situated in the air ow, trips at 70 °C and has automatic reset
3. TSA120 is situated in the air ow, trips at 120 °C and has manual reset i HCE and HMI
Function / component Description
Temperature sensors In the supply air duct to measure supply air temperature
Control of external cooling unit via start/stop signal and on-demand regulation 0–10 V
HCW - External water heating coil
CCW - External cold water coil
HCE - External electrical heating coil
MXCU - External cooling control