
14
VEX340: Control system
EXact control system - List of functions
Function / component Description
Standard
Accessory
Filter monitor Pressure sensors for monitoring the pressure drop across the lters – alarm for a
fall more than the value set and "Early Warnings"
Bypass In the case of modulating bypass of extract air, the heat recovery is reduced to
maintain the desired supply air temperature
Temperature sensors 1) In the extract air spigot to measure/control room temperature
2) In the exhaust air spigot to measure exhaust air temperature
3) In the outdoor air spigot for outdoor air temperature compensation and
night-time cooling
4) In the supply air spigot to measure/control supply air temperature
5) Duct temperature sensor
6) Room temperature sensor
Overheating protection If there is a danger of the motors or frequency converters overheating the unit will
shut off – manual reset.
Fire alarm Fire thermostats (40/50/70°C), smoke detector and other re detection switches
can be connected. In the case of a tripped re alarm, the unit’s functions are adjustable
.
Closing damper, outdoor air
(requirement for water
heating coil)
The damper is tted in the outdoor air duct – it shuts when the unit stops –
available with a spring-return motor
(
)
Closing damper, exhaust air The damper is tted in the exhaust air duct – it shuts when the unit stops – available
with spring-return motor
Regulating temperature Regulation of the supply air temperature
Regulation of the room temperature
Compensation functions Outdoor air temperature compensation
Airow reduction
Outdoor airow compensation
Summertime compensation
CO
2
compensation
Humidity compensation
Night-time cooling The unit can be set to start at night to cool the building
Frost protection Automatic energy-saving feature for preventing icing in the counter ow heat
exchanger
Control panel Panel for operation at user, technician and specialist level
Weekly clock For setting the times required for changes between indoor air quality levels
Bus communication Modbus RTU
Modbus TCP/IP
LONWORKS
®
Web server Integrated web server allowing control and monitoring over the internet.
Cooling recovery On-demand cold recovery
Constant pressure regulation Possible for both extract and supply air
Motion sensor (PIR) For automatic control of indoor air quality level
Airow measurement Airow shown in control panel
Indoor air quality levels Timer-controlled (comfort, standby, economy, off)
Manual
Alarm log Displays the last 100 alarms
Timers Supply air motor, extract air motor motor
Alarm relay Relay for external alarm
The table below describes the control system functions. More detailed descriptions of selected functions are shown on the following pages.
Comentários a estes Manuais